Residential Codes (IRC)

Question: 

I am looking for a 1-hour roof/ceiling assembly for wood truss construction. I would like to apply the drywall directly to the bottom of the truss and also have insulation for sound control. Is this possible without using channels and what UL number would I use?

Question: 

Would you please inform me of the specified requirements of the size and the amount of nail attachments from the truss to the top plate?

Question: 

We have a local builder wishing to use floor trusses with a 2-hour assembly. I have shown him the 2-hour design on pages 17-27 of the second edition of SBCA’s Metal Plate Connected Wood Truss Handbook. Is this assembly UL approved? If so, what is the design number?

Question: 

How do you evaluate whether a metal plate connected truss is still usable after exposure to fire? Are there any recommended tests?

Question: 

Is a Class A fire rating (provided by our liquid spray-on fire retardant) acceptable in certain situations?

Question: 

My company supplied roof trusses for a hotel project. The building inspector shut the project down because the trusses were not designed to account for additional snowdrift loading. The construction plans did not contain any snowdrift loading information. The architect is claiming it is our responsibility to determine drift loading, therefore we must fix the problem. Do you have any documentation to help us dispute the architect’s claim?

Question: 

We recently received bids on a school project, which referenced UL P523. This assembly used light-gauge steel trusses. We noted on the drawing that we could accept an alternate design using wood trusses in lieu of light-gauge steel framing, if the alternate design could meet the fire ratings.

Question: 

I was wondering if you have any information or anecdotes relating to the deflection performance of long span scissors trusses? We recently sold a job with 70 ft. long scissors trusses. The customer is in the process of installing the trusses and doesn't like the deflections he is seeing. To make matters worse, the scissors trusses are framing into a valley set (which we provided) that is erected on 35 ft. Howe trusses. The Howe trusses are exhibiting very little deflection. Any ideas?

Long span trusses can pose significant risk to installers. The dimensions and weight of a long span truss can create instability, buckling and collapse of one or many trusses, if not handled, installed, restrained and braced properly. As such, they require more detailed safety and handling measures than shorter span trusses. This research report provides guidelines for proper handling and installation of long span trusses for both wood and cold-formed steel.

ASCE/SEI 7-16 Minimum Design Loads for Buildings and Other Structures has revised Chapter 30 regarding Components & Cladding (C&C) wind loads on roofs. This report clarifies the type and scope of changes being made that will also change in the 2018 edition of the model building codes.